Related Question
Class B trip curve:
The MCB with class B trip characteristics trips instantaneously when the current flowing through it reaches between 3 to 5 times rated current. These MCBs are suitable for cable protection.
Hence, For 16 A current Type B MCB disconnect fault at 3*16 = 48 A to 5*16 = 80 A.
A form of AC testing that applies voltage and measures the leakage/loss current of electrical insulation.
It is a type of insulation testing used to evaluate the integrity of electrical insulation.
Thermistors are ideal when measuring a single point temperature that is within 50°C of ambient.
If the temperatures are excessively high or low, a thermistor will not work.
Most thermistors work best in the range between -55°C and +114°C.
Sensitivity of thermistor is high.
Span value of thermistor is low.
P = S*cosφ
S = P/cosφ
S = 300/0.5
S = 600 kVA
For same kVA rating and unity power factor,
P = 600*1
P = 600 kW
Pextra = 600 - 300
Pextra = 300 kW
Here, Y phase is shorted,
Equation of 3-phase power = √3*VL*IL*cosφ
IL = P/(√3*VL*cosφ)
= 8000/(√3*400*0.8)
= 12.55 A
Phase impedance = Vp/Ip
= 460/(√3*12.55)
= 21.16 ohm
cosφ = 0.8, So φ = 37 degree.
Here Impedance of Y phase is shorted,
So, Neutral point and Y phase at same potential,
Three line voltages are given by,
Vry = 460∟0°
Vyb = 460∟120°
Vbr = 460∟-120°
Here N and Y phase at same potential,
Ir = (460∟-120°)/(21.16∟37°)
= -21.7∟83° A
Ib = (-460∟120°)/(21.16∟37°)
= 21.7∟-157° A
Ib = -(Ir + Iy)
= -21.7∟83° + 21.7∟-157°
= 37.6∟53° A