Related Question
Here,
Cosφ = 0.397
P = 30 kW = √3*V_L*I_L*cosφ
V_L*I_L = 30kW/(√3*0.397) = 43628.48 VA
Readings of wattmeter W1 = V_L*I_L*cos(30+φ)
Readings of wattmeter W2 = V_L*I_L*cos(30-φ)
Conductor with higher temperature ratings, provide the ampacity is determined based on the 60°C ampacity of the conductor.
Aerial bundled cables/conductors are overhead power lines using several insulated phase conductors bundled tightly together, usually with a bare neutral conductor.
This contrasts with the traditional practice of using uninsulated conductors separated by air gaps.
This variation of bundled conductors utilizes the same principles as overhead power lines, except that they are closer together to the point of touching but each conductor is surrounded by an insulating layer
The load current is inversely proportional to the power factor, if power is constant
Lower the power factor, higher is the load current.
kVA rating of the equipment is inversely proportional to power factor.
The smaller the power factor, the larger is the kVA rating.
Therefore, at low power factor, the kVA rating of the equipment has to be made more, making the equipment larger and expensive.
To transmit or distribute a fixed amount of power at constant voltage, the conductor will have to carry more current at low power factor. This necessitates large conductor size.
The large current at low lagging power factor causes greater voltage drops in alternators, transformers, transmission lines and distributors. This results in the decreased voltage available at the supply end.