The capacity of reactor = 50 MVAr when it is operated at 415 kV.
Impedance of reactor = V2/MVAr = (415*415)2/50 = 3444.5 Ω
For 400 kV,
Reactive power observed = (400*400)/3444.5
= 46.45 MVAR
Or
VAr capacity of capacitor or reactor is proportional to V²
Related Question
Class B trip curve :
The MCB with class B trip characteristics trips instantaneously when the current flowing through it reaches between 3 to 5 times rated current. These MCBs are suitable for cable protection.
Class C trip curve:
MCB with class C trip characteristics trips instantaneously when the current flowing through it reaches between 5 to 10 times the rated current. Suitable Domestic and residential applications and electromagnetic starting loads with medium starting currents.
Class D trip curve:
MCB with class D trip characteristics trips instantaneously when the current flowing through it reaches between Above 10 (excluding 10) to 20 times the rated current. Suitable for inductive and motor loads with high starting currents.
Class K trip curve:
MCB with class K trip characteristics trips instantaneously when the current flowing through it reaches between 8 to 12 times the rated current. Suitable for inductive and motor loads with high inrush currents.
Here,
Cosφ = 0.397
P = 30 kW = √3*V_L*I_L*cosφ
V_L*I_L = 30kW/(√3*0.397) = 43628.48 VA
Readings of wattmeter W1 = V_L*I_L*cos(30+φ)
Readings of wattmeter W2 = V_L*I_L*cos(30-φ)
Buchholz relay is gas operated relay.
It will operate when internal fault occurs in transformer.
It is placed between tank to main conservator.
It has two contacts trip and alarm.
Use of Buchholz relay in distribution transformer is not economical.
For lagging power factor = (IR*cosφ + IXsinφ)/V_r
For leading power factor = (IR*cosφ - IXsinφ)/V_r
Zero voltage regulation occurs on leading power factor only.