Class B trip curve:
The MCB with class B trip characteristics trips instantaneously when the current flowing through it reaches between 3 to 5 times rated current. These MCBs are suitable for cable protection.
Hence, For 16 A current Type B MCB disconnect fault at 3*16 = 48 A to 5*16 = 80 A.
Related Question
Equivalent resistance of the circuit, Req = (750|| 600 || 200)
Req = 125 Ω
Current from source = 1 A
Source voltage = 1*125
Source voltage = 125 V
As per the key statistics data of IEA With electricity consumption reached to 1,164 TWh in the country till November 2019, India ranked third among the top ten electricity consuming countries across the globe.
The ratio of full load current to short circuit current = 1/5
Xsc = j/(1/5)
External reactance required = j*((1/5) - 0.05))
= j*0.15 pu
Full load current = (30*1000)/(√3*11)
= 1574.6 A
Per unit reactance = j*0.15 = (I*Xr)/V
j*0.15 = (1574.6*Xb)/((11/√3)*1000))
= 0.60 ohm